Electrical Engineering Power Systems

Explore top LinkedIn content from expert professionals.

  • View profile for Amine ECH-CHAMALI

    Project Engineer | Utility-scale BESS & Solar PV | Power Systems

    1,896 followers

    ⚡ BESS Energy Losses: What Really Happens Between the Grid and Your Battery Nameplate capacity sells projects. Delivered energy pays for them. Yet most BESS discussions stop at cell level efficiency or $/kWh pricing, long before anyone maps the full AC/AC energy journey. Here is what a complete energy flow balance looks like for a 5 015 kWh grid connected BESS system. 🔍 Think in flows, not in boxes A grid connected BESS is not simply a battery. It is a chain of energy conversion and transport stages, each introducing losses that compound across every charge and discharge cycle. 📥 CHARGING (The battery never sees full grid energy) Grid draw: 5 477 kWh ▸ MV transformer & AC cabling: 54 kWh ▸ PCS conversion (AC → DC): 108 kWh ▸ DC busbars & cabling (I²R): 27 kWh ▸ Battery internal losses: 211 kWh Net stored at cell level: 5 077 kWh Each upstream component must be rated against gross grid intake, not net stored energy. Undersizing here leads to thermal stress, premature aging, and hidden yield loss. 📤 DISCHARGING (Further losses before the grid sees anything) Available at cell level: 5 077 kWh ▸ Battery internal losses: 203 kWh ▸ DC busbars & cabling (I²R): 24 kWh ▸ PCS conversion (DC → AC): 97 kWh ▸ MV transformer & AC cabling: 47 kWh Net delivered to grid: 4 706 kWh 📊 What actually matters Total system losses per cycle: 771 kWh AC/AC round-trip efficiency: 85.9% This 85.9% not the nameplate is what your revenue model and dispatch strategy should be built on. 🛠️ Four levers that control these losses ▸ PCS topology: single Vs two stage conversion carries a real efficiency delta across the load curve, worth hundreds of MWh over a 15 year asset life. ▸ DC cable sizing I²R losses scale with the square of current. Undersized DC runs are invisible during commissioning and persistent across every cycle. ▸ MV transformer specification no-load losses accumulate even during standby. Optimizing for peak throughput may be the wrong match for your dispatch pattern. ▸ Thermal management: elevated cell temperature increases internal resistance, compounding losses in both directions on every cycle. 💡 The core principle Two systems with identical battery capacity, same chemistry, same SoC window can deliver meaningfully different energy to the grid based solely on system level design decisions. Energy-flow modeling at concept stage is not optional. It is what separates a financial model grounded in physics from one built on nameplate assumptions. The goal is not to maximize stored energy. It is to minimize what is lost between grid-in and grid-out. Working on BESS sizing or performance modeling? Drop your thoughts in the comments 👇 #BESS #BatteryStorage #EnergyStorage #GridScale #PowerEngineering #EnergyModeling

  • View profile for Shubham Sharma

    Sales Manager - Utility Business (India) | Hoymiles | BESS | PCS

    22,940 followers

    #100days100BESSLearnings Day 56: The Four-Quadrant Function of a BESS A BESS is a far more sophisticated grid asset than a simple energy source. Its true value lies in the agility of its PCS, which is capable of operating in a four-quadrant function. This advanced capability is fundamental to how a BESS provides multiple grid services and earns a variety of revenue streams. The P-Q Plane: A Visual Guide To understand the four-quadrant function, we first need to look at the P-Q Plane. This is a two-dimensional graph where: --The horizontal axis (P) represents Active Power (measured in MW), which is the power that does real work, such as powering lights and motors. --The vertical axis (Q) represents Reactive Power (measured in MVAR), which is the power required to establish and maintain magnetic fields in electrical equipment. The BESS’s ability to control both P and Q independently, across both positive and negative values, is what defines its four-quadrant capability. The Four Quadrants Explained Each quadrant on the P-Q plane represents a unique operational mode for the BESS: #Quadrant I: Positive P, Positive Q (+P,+Q) Function: The BESS is discharging Active Power (+P) and simultaneously injecting Reactive Power into the grid (+Q). Use Case: Providing a combination of energy to the grid and voltage support, which is crucial for stabilizing the grid during high load periods. #Quadrant II: Negative P, Positive Q (−P,+Q) Function: The BESS is charging and absorbing Active Power from the grid (−P) while still providing Reactive Power (+Q). Use Case: This mode is particularly useful for absorbing excess power from renewables while simultaneously providing voltage support to the local grid, preventing a voltage collapse. #Quadrant III: Negative P, Negative Q (−P,−Q) Function: The BESS is charging and absorbing Active Power (−P) and also absorbing Reactive Power (−Q). Use Case: This is the ideal mode for charging from a strong grid. It can be used to absorb power from a high-voltage grid and reduce system voltage, ensuring that the grid stays within its operational limits. #Quadrant IV: Positive P, Negative Q (+P,−Q) Function: The BESS is discharging Active Power (+P) but simultaneously absorbing Reactive Power (−Q). Use Case: This is a less common but still critical mode. It can be used to inject active power into a grid that has an excess of reactive power, helping to prevent an over-voltage condition. Why It's Essential for BESS The 4-quadrant function is the key that unlocks the full value of a BESS. Without it, a BESS would be limited to only charging and discharging active power. This capability allows a BESS to provide a wide range of ancillary services simultaneously, such as frequency regulation (P) and voltage support (Q), thereby increasing its revenue streams and making it a more profitable and versatile asset for the grid. #BESS #FourQuadrant #PCS #GridServices #ActivePower #ReactivePower #EnergyStorage #100days100BESSLearnings

  • View profile for Doug Millner P.E.

    Power System training be provided starting July. Contact for details. $225/hr -Expert Power Engineer- Relaying, Arc Flash, Power System Studies, NERC Compliance

    28,940 followers

    What is Resonant Grounding or Peterson Coils? This is an interesting topic because it is something that is not at all common in the U.S. but is more common in Europe, China, Australia, and India. In the U.S., medium- and high-voltage networks are typically solidly grounded or grounded through an impedance. Peterson Coils or resonant grounding is neither of these. What is affected by how a system is grounded? The most obvious thing is the amount of available fault current for ground faults (single-line-to-ground, double-line-to-ground, etc.). These faults pull ground current up through a source, like a zig-zag or a delta-wye transformer or even just capacitance to ground, and put it back into the ground at the ground fault, completing the loop. Putting an impedance at the ground source makes this loop have more impedance and reduces the available ground current. Other things that can affect this ground fault loop's impedance are line impedances to the fault, very resistive or rocky soil, frozen ground, or even a high impedance fault, which will affect the magnitude of the ground fault current. The trade-off, though, to choking back the fault current is that it makes the system more susceptible to transient overvoltages during faults. This is most pronounced on ungrounded systems. If a phase is faulted on an ungrounded system, very little fault current is fed to the fault (only due to capacitance to ground), but the voltage on the other two healthy phases increases by 173% to ground, and there is a risk of developing much higher voltages (around 400%) if there is intermittent arcing. What does this have to do with Peterson Coils? Systems that use resonant grounding are not solidly grounded, impedance grounded, or even ungrounded. The ground source path is through the Peterson Coil. What does the Peterson Coil do? The Peterson Coil is an inductance tuned to the line-to-ground capacitance of the transmission line. This creates the situation where X_Peterson_Coil = X_Line_capacitance. Since these two elements are in parallel with the single-line-to-ground fault, they act as parallel resonant filters tuned to the grid frequency, 50 or 60 Hz. Series resonance acts like a very low impedance path, but parallel resonance acts like a high impedance path. This, in effect, causes the ground impedance to be very high, including the line capacitance to ground, and is able to reduce the ground current available at the fault to near zero, extinguishing the arc. What is the benefit of this? If a tree or something falls into a line and faults a phase, the system is allowed to still operate. Ungrounded systems can offer this too, but they don't have a means to prevent arcing until crews arrive to resolve the issue, and at the least, the two other healthy phases would see a 173% increase in voltage. The Peterson Coil is able to avoid these things through parallel resonance. #utilities #electricalengineering #renewables #energystorage

  • View profile for Jonas Kristiansen Nøland

    Professor at NTNU

    14,787 followers

    The Spanish government recently released its evaluation report investigating the causes of Europe's worst blackout on April 28, 2025. Unfortunately, mainstream narratives oversimplify the findings, potentially misleading the public about the actual root causes of this severe event. In science, we recognize the importance of avoiding the "fallacy of oversimplified cause," which involves wrongly attributing an event to a single factor while ignoring crucial underlying factors. Current media narratives highlight only voltage regulation issues while dismissing the essential role played by insufficient system inertia. Indeed, the official report clearly states that the blackout had a "multifactorial origin." My academic colleague in Spain, Luis Badesa, has provided important insights into this complexity. He hypothesized early on that the severe overvoltages initiating the blackout were triggered by control actions—specifically power system stabilizers (PSSs) and inverter-based controls—implemented to damp inter-area frequency oscillations. Additionally, reactive power management was significantly compromised. Renewable, cogeneration, and waste (RCW) power plants, operating in constant power factor mode, altered their reactive power outputs, exacerbating voltage oscillations during frequency disturbances preceding the initial generation losses. Badesa's preliminary analysis highlights critical questions about why these oscillations were insufficiently damped, suggesting their persistence directly impacted voltage control and system stability. He notes that overvoltages in southwest Spain were likely connected to these prior oscillations, describing the blackout vividly: “This wasn’t one failure. It was a cascade, like falling off a cliff, breaking a leg, and getting attacked by a bear.” Essentially, actions intended to stabilize frequency inadvertently undermined voltage regulation and reactive power management processes, causing severe overvoltages that set off a cascade of generation losses. Each disconnection worsened reactive power imbalances, amplifying voltage spikes and leading to more generator trips—culminating in a full-scale blackout. Understanding this complex chain of events is crucial. Oversimplifying the narrative risks obscuring critical lessons we must learn to build a more resilient power grid. For further insights: [1] https://lnkd.in/gcRSAHBM [2] https://lnkd.in/g2ew6JAr  [3] https://lnkd.in/gz555CqK

  • View profile for Hardik Sheth

    Utility-Scale Solar EPC & BESS Projects| 1000+ MW | CleanTech | CPaaS | Voice AI | India | Middle East | Africa | US

    14,311 followers

    𝐄𝐯𝐞𝐫𝐲𝐨𝐧𝐞 𝐓𝐚𝐥𝐤𝐬 𝐀𝐛𝐨𝐮𝐭 𝐁𝐄𝐒𝐒 — 𝐀𝐥𝐦𝐨𝐬𝐭 𝐍𝐨 𝐎𝐧𝐞 𝐓𝐚𝐥𝐤𝐬 𝐀𝐛𝐨𝐮𝐭 𝐭𝐡𝐞 𝐏𝐂𝐒 (𝐀𝐂 𝐁𝐥𝐨𝐜𝐤) Most Battery Energy Storage conversations stop at: battery chemistry, container MWh and $/kWh headlines But in real projects, the 𝐏𝐂𝐒 𝐚𝐧𝐝 𝐀𝐂 𝐛𝐥𝐨𝐜𝐤 decide whether your BESS actually makes money. If batteries are the engine, PCS is the drivetrain. 𝐖𝐡𝐚𝐭 𝐭𝐡𝐞 𝐏𝐂𝐒 (𝐏𝐨𝐰𝐞𝐫 𝐂𝐨𝐧𝐯𝐞𝐫𝐬𝐢𝐨𝐧 𝐒𝐲𝐬𝐭𝐞𝐦) 𝐑𝐞𝐚𝐥𝐥𝐲 𝐃𝐨𝐞𝐬 PCS is not “just an inverter.” It is responsible for: •  DC ↔ AC conversion •  grid synchronization •  voltage & frequency control •  reactive power support •  fault ride-through •  protection and islanding logic Without a properly designed PCS + AC block, your battery is just an expensive DC box. 𝐓𝐲𝐩𝐢𝐜𝐚𝐥 𝐏𝐂𝐒: • PCS rating: 2.5–5 MW per unit (most common today) • DC/AC ratio: typically 1.2–1.5 • Round-trip efficiency impact: PCS alone can swing 1.5–3% • Response time: Grid-forming PCS: <20 ms Grid-following PCS: 50–100 ms 𝐖𝐡𝐚𝐭’𝐬 𝐀𝐜𝐭𝐮𝐚𝐥𝐥𝐲 𝐈𝐧𝐬𝐢𝐝𝐞 𝐚𝐧 𝐀𝐂 𝐁𝐥𝐨𝐜𝐤 •  PCS (bi-directional inverter) •  MV transformer (33 kV / 66 kV typical) •  MV switchgear & protection •  EMS interface •  Auxiliary power & cooling •  Often 15–25% of total BESS CAPEX Cheap batteries won’t save a bad PCS decision. 𝐖𝐡𝐚𝐭 𝐀𝐜𝐭𝐮𝐚𝐥𝐥𝐲 𝐌𝐚𝐭𝐭𝐞𝐫𝐬 𝐖𝐡𝐞𝐧 𝐒𝐞𝐥𝐞𝐜𝐭𝐢𝐧𝐠 𝐏𝐂𝐒 1. Grid-forming vs Grid-following 2. Overload capability 3. Harmonics & compliance 4. Efficiency curve (not peak efficiency) 5. Vendor bankability & track record 𝐅𝐢𝐧𝐚𝐥 𝐓𝐡𝐨𝐮𝐠𝐡𝐭 The future of BESS isn’t decided by who has the cheapest cells. It’s decided by: •  who controls the grid interface •  who delivers stability, not just storage •  who understands the AC block as infrastructure, not an accessory If you’re still choosing BESS vendors based only on $/kWh, you’re already behind. Visit👉https://alendei.energy/ for 𝐒𝐨𝐥𝐚𝐫, 𝐁𝐄𝐒𝐒 𝐄𝐏𝐂𝐬, 𝐈𝐧𝐯𝐞𝐬𝐭𝐦𝐞𝐧𝐭, & 𝐂𝐨𝐧𝐬𝐮𝐥𝐭𝐚𝐭𝐢𝐨𝐧 #UtilityScaleSolar #OnshoreWind #SolarEPC #WindEPC #ReNewPower #AdaniGreen #TataPowerRenewables #Suzlon #InoxWind #JSWEnergy #NTPC #SECI #SterlingAndWilson #LarsenAndToubro #ACWAPower #Masdar #DEWA #EWEC #NEOM #AmeaPower #AlFanar #CEPCO #SaudiEnergy #UAEEnergy #LekelaPower #Globeleq #Azuri #AfreximBank #KenGen #Eskom #ZESCO #AfricaIPP #NextEraEnergy #Invenergy #PatternEnergy #AESCorporation #NRGEnergy #DukeEnergy #Exelon #DominionEnergy #Enbridge #BrookfieldRenewables #AlgonquinPower #HydroOne #OntarioPowerGeneration #EDFrenewables #EDPRenewables #BPAlternativeEnergy #ClearwayEnergy #ApexCleanEnergy #FirstSolar #TrinaSolar #CanadianSolar #JinkoSolar #BechtelEPC #BlackAndVeatch #BurnsAndMcDonnell #RESAmericas #Vestas #VestasAmericas #GErenewables #SiemensGamesa #Nordex #NordexAcciona #TeslaEnergy #EatonEnergy #ABBPowerGrids #AtlasRenewableEnergy #EnelGreenPower #Neoenergia #Energisa

  • View profile for Madjer Santos, PE, P.Eng., PMP, MBA

    Director | Power Engineering & Project Delivery | Substation Design | Protection and Control (P&C) | System Protection | Transmission & Distribution (T&D) | Renewable Energy | Leadership | 18+ years in the Power Industry

    17,274 followers

    If you have ever looked at a protection scheme for an ungrounded or high-resistance grounded system, you have probably seen a broken delta VT arrangement feeding a 59N element. Most engineers know it measures 3V0. Fewer can explain why. Here is the reasoning. Under healthy balanced conditions, the three phase-to-ground voltages are equal in magnitude and displaced by 120 degrees. Their phasor sum, Va + Vb + Vc, is approximately zero. In the broken delta, the VT secondaries are connected in series to form a closed loop with one corner left open. Because the phasor sum is near zero, the voltage across that open corner is near zero. Now a ground fault occurs. On an ungrounded or high-resistance grounded system, the neutral point shifts. The faulted phase voltage drops while the healthy phase voltages rise relative to ground. The three phase-to-ground voltages are no longer balanced. Their phasor sum no longer cancels. That residual, Va + Vb + Vc, is by definition three times the zero-sequence voltage: 3V0. And that is what appears across the open corner of the broken delta. A residual overvoltage element, often designated 59N or 59G depending on the relay platform, monitors that voltage. When 3V0 exceeds the set threshold, the relay detects a ground fault, not through current, but through the zero-sequence voltage the broken delta makes visible. This matters because on these systems, fault current is intentionally limited. Conventional overcurrent protection has no reliable signal to work with. The broken delta gives protection a detection path that would otherwise not exist. I have seen in the past installations where the broken delta wiring was incorrectly terminated (secondaries connected in the wrong phase sequence) producing a standing residual voltage under healthy conditions and masking the real 3V0 signature during faults. A small wiring error in this circuit can defeat the entire ground fault detection scheme. That is why this is worth understanding from first principles, not just memorizing. For those working with ungrounded or high resistance grounded systems: what 59N threshold do you typically use, and have you ever had to troubleshoot a broken delta circuit that was not reading as expected?

  • View profile for MOHAMMED MUNAF

    Senior Manager-Projects at Sunsure Energy |Ex-Amperehour|Ex-Amplus Solar(PETRONAS Group)| Ex-GE T&D India Limited| Project Management| Asset Management| Testing & Commissioning||Renewable Energy & Storage Solutions||BESS

    9,828 followers

    🔌 Inverter (PCS) Sizing for Battery Energy Storage System (BESS) The Power Conversion System (PCS), or inverter, is the heart of any BESS — enabling seamless power exchange between batteries and the grid or load. Whether the application is energy shifting, peak shaving, frequency regulation, or black start, correct PCS sizing ensures system reliability, efficiency, and compliance. ✅ 1. Key Parameters for PCS Sizing 📥 Input Data Required: 1. Required Output Power (kW/MW) – Based on system demand 2. Energy Capacity (kWh/MWh) – Total energy to be processed 3. Discharge Duration (hours) – Continuous operation time 4. Battery Bank Voltage (DC side) – Typically 750V to 1500V 5. AC Output Voltage (LV/MV) – 400V / 690 /800 V, stepped up if required 6. Efficiency – Round-trip efficiency affects final sizing 7. Overload & Surge Rating – For transient loads and grid events 8. Black Start Capability – Inverter start loads without grid reference as per requirement. 9. Grid Compliance – IEEE 1547, UL 1741, IEC 62477, CEA, etc. 🧮 2. Step-by-Step PCS Sizing Process ✅ Step 1: Determine Required Power Rating PCS Power (kW) = Battery Energy (kWh) ÷ Discharge Time (hours) ✅ Step 2: Adjust for Efficiency & Buffer Adjusted PCS Size = PCS Power ÷ Efficiency × Safety Factor Example: If Energy = 4000 kWh, Duration = 2 hrs, Efficiency = 0.96, Safety Factor = 1.1 → PCS Size = (4000 ÷ 2) ÷ 0.96 × 1.1 = 2291.67 kW ✅ Step 3: Match DC Voltage Range • Ensure battery bank voltage matches PCS DC input window (e.g., 1000–1500V DC) • Consider voltage drop at low SoC ✅ Step 4: Select AC Output & Interface Voltage • LV (400V/690/800 V) or MV via step-up transformer • Compliant with local grid code & short circuit rating ✅ Step 5: Include Black Start Capability (if needed) • PCS must operate without grid signal and generate its own voltage/frequency reference • Critical for islanded systems, emergency power, or substation restoration ✅ Step 6: Choose Inverter Topology • Centralized vs modular PCS • Grid-forming vs grid-following depending on application 🛠️ Whether for grid-tied operation, backup, or black start functionality, right-sizing your PCS = system stability + long-term performance. #BESS #PCSSizing #BlackStart #InverterSizing #EnergyStorage #GridSupport #Renewables #BatteryEnergyStorage #ProjectEngineering #PowerConversion #CleanEnergy #ResilientGrid

  • View profile for Md. Kalimuddin

    MEP Manager Project /Co-ordinator at LAB SERVICES &SOLUTIONS Pvt. Ltd.

    7,076 followers

    Difference Between kVA and kW Aspect kVA (Kilovolt-Ampere) kW (Kilowatt) Definition kVA represents the apparent power, which is the total power used in an electrical system (including both active and reactive power). kW represents the real power, which is the actual power consumed by electrical equipment to perform useful work. Formula kVA = kW / Power Factor (PF) kW = kVA × Power Factor (PF) Power Type Apparent Power (Total Power) Real Power (Useful Power) Usage Used for sizing generators, transformers, and UPS systems. Used for calculating electricity bills and actual power usage. Power Factor Influence Not affected by power factor. Affected by power factor (lower PF means lower real power output). Example A transformer rated at 100 kVA can deliver different kW values depending on the power factor: - At 0.8 PF: kW = 100 × 0.8 = 80 kW - At 0.9 PF: kW = 100 × 0.9 = 90 kW A 60 kW motor running at 0.85 PF requires: - kVA = 60 / 0.85 = 70.6 kVA Example Calculation: Case 1: Generator Sizing A 100 kW load with a power factor of 0.8 requires: kVA = 100 / 0.8 = 125 kVA generator. Case 2: Transformer Load A 200 kVA transformer with a power factor of 0.9 can supply: kW = 200 × 0.9 = 180 kW of real power. Key Takeaway: kVA is used for capacity planning (transformers, generators). kW is used for billing and actual power consumption. Power factor plays a crucial role in converting between kVA and kW.

  • View profile for Igor Morozov

    VP, Data Center Power Solutions @ SolarEdge | Building the 800VDC architecture for AI factories | Hardware at scale + Kellogg EMBA

    3,949 followers

    The Hidden Megawatt: Why We Are Engineering Our Own Gridlock ⚡🏗️ Everyone is racing to secure the next grid connection 🔌 Almost nobody is asking how much compute is being left on the table with the connection they already have. I call it the Hidden Megawatt. In a traditional data center power chain, electricity is converted about five times between the grid and the GPU. Each stage adds loss, heat, cost, and failure risk. By the time power reaches the chip, roughly 5 to 7 percent of total facility capacity is already gone, burned as heat before a single token is produced ♨️ At 100 MW, that equals an entire row of GPU racks you paid for but never use 🖥️ At gigawatt scale, it becomes a full building of stranded compute capacity 🏢 This would matter less if new grid capacity were easy to obtain. It is not. In major hubs, large connections can take many years to secure ⏳ While the industry waits for new megawatts, existing megawatts quietly disappear inside legacy conversion chains. This is an architecture problem 🧠 An 800 VDC architecture cuts the conversion chain down to a minimal path ⚡ Converting medium voltage AC directly to high voltage DC and distributing DC natively turns more incoming watts into usable compute instead of heat. The ecosystem is already shifting 🚀 Next generation AI racks, high density power shelves, and 800 VDC reference designs are entering deployment now. The most valuable megawatt is often not the next one you are trying to connect. It is the one you can recover inside your existing facility 💡 No permits 📄 No queue 🚦 No multi year wait ⏱️ Just better power architecture ⚡ #DataCenterDesign #800VDC #AIInfrastructure #EnergyEfficiency #DataCenterDC #DataCenterSST #SolarEdgeSST #DataCenter800VDC

Explore categories